Enclosed Sentinel 300P.
Input supply 10/120/220/240 VAC (50 Hz/60 Hz).
Output 10 A at 12/24 V.
Analog ammeter and voltmeter.
Specifications
Power Supply
Alternate Current (AC) Operating Voltage |
N/A 95 to 250 V |
Operating Frequency |
N/A 47 to 63 Hz |
Direct Current (DC) Charge Output
Direct Current (DC) Nominal Voltage1 | N/A 12 V24 V |
Maximum Current Limit |
N/A 10 A |
Voltage Ripple |
N/A <1 % |
Line Regulation |
N/A <2 % |
Load Regulation |
N/A <2 % |
Rating (All Relays)
Maximum Current Rating at 30 Direct Current (DC) Voltage2 | N/A 1 A |
Standards for Maximum Current Rating at 30 Direct Current (DC) Voltage |
N/A UL Class 2 |
Physical
Operating Temperature |
N/A -40 to 60 ºC-40 to 140 ºF |
Display Viewability (Liquid Crystal Display (LCD) Models) |
N/A 0 to 50 ºC32 to 122 ºF |
Relative Humidity |
N/A 20 to 90 % |
Electrical Safety |
N/A 2006/95/EC |
Electromagnetic Compatibility |
N/A 2004/108/EC EN 55022 Class B (EN 61000-6-1, EN 61000-6-3) |
UL Approvals |
N/A BBGQ: UL1236, CSA22.2 no. 107.2 BBHH: UL1236 SE |
Dimensions
Overall Width (W) |
N/A 6.50 in165 mm |
Overall Height (H1) |
N/A 11.81 in300 mm |
Overall Height (H2) |
N/A 3.15 in80 mm |
Overall Depth (D1) |
N/A 4.92 in125 mm |
Overall Depth (D2) |
N/A 5.12 in130 mm |
Fixing Holes (X) |
N/A 2.50 in63.5 mm |
Fixing Holes (Y) |
N/A 11.25 in285.5 mm |
Weight |
N/A 4.4 to 4.6 lb2.0 to 2.1 kg |
Standard Output Calibration
AutoBoost
AutoBoost |
N/A
Triggered automatically on low charge levels, or manually by remote switch, AutoBoost temporarily increases the charge voltage before returning to float mode. Equalizing battery cell charge without overcharge and gassing, AutoBoost maximizes cell capacity and life. |
Temperature Compensation
Temperature Compensation |
N/A
For remote charger control, and signaling of charge fail, high/low battery volts and mains fail faults. Standard output functions are NFPA 110 compliant. Non-standard input/output functions available to special order. |
Flexible Configuration
Flexible Configuration |
N/A
For remote charger control, and signaling of charge fail, high/low battery volts and mains fail faults. Standard output functions are NFPA 110 compliant. Non-standard input/output functions available to special order. |
Inputs and Outputs
Inputs and Outputs |
N/A
Tested and approved by UL to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |
Display, Instrumentation and Communication
Display, Instrumentation and Communication |
N/A
Tested and approved by UL to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |
Note
Note |
N/A
Tested and approved by UL to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |
- 1 Programmable
- 2 Resistive load