Alternate Current (AC) Operating Voltage |
N/A 95 to 265 V |
Operating Frequency |
N/A 47 to 63 Hz |
Direct Current (DC) Nominal Voltage |
N/A 24 V |
Maximum Current Limit |
N/A 5 A |
Voltage Ripple |
N/A <1 % |
Line Regulation |
N/A <2 % |
Load Regulation |
N/A <2 % |
Control Input |
N/A Close to -DC to Activate Digital (Switch) Input Programmable Function |
Alarm Output |
N/A Programmable Function Relay Switched +DC |
Maximum Current Rating at 30 Direct Current (DC) Voltage (Alarm Output) |
N/A 1 A |
Protective Cover Material |
N/A 1050 Aluminum |
Protective Cover Thickness |
N/A 1.2 mm |
Operating Temperature |
N/A -30 to 60 ºC-22 to 140 ºF |
Storage Temperature |
N/A -40 to 60 ºC-40 to 140 ºF |
Relative Humidity |
N/A 20 to 90 % |
Electrical Safety |
N/A 2006/95/EC (EN 60065) |
Electromagnetic Compatibility |
N/A 2004/108/EC (EN 61000-6-2, EN 61000-6-4) |
Overall Width (W) |
N/A 4.28 in108.6 mm |
Overall Height (H) |
N/A 5.31 in135 mm |
Overall Depth (D) |
N/A 2.17 in55 mm |
Fixing Holes (X) |
N/A 3.90 in99 mm |
Fixing Holes Diameter (F) |
N/A 0.22 in5.65 mm |
Weight |
N/A 1.65 lb0.75 kg |
Features |
N/A
|
AutoBoost |
N/A A' option models include a control input and alarm output, both with configurable functions. The input can be configured for use with panel relay circuits or operator switches, giving additional control over the output, e.g. AutoBoost initiation and termination. The alarm relay output can be configured to operate during a one or more (up to 7) fault conditions: mains fail, DC connection error, battery missing, temp sensor short, low battery volts, high battery volts, charge fail. |
Alarm Output and Control Input ('A' Option) |
N/A A' option models include a control input and alarm output, both with configurable functions. The input can be configured for use with panel relay circuits or operator switches, giving additional control over the output, e.g. AutoBoost initiation and termination. The alarm relay output can be configured to operate during a one or more (up to 7) fault conditions: mains fail, DC connection error, battery missing, temp sensor short, low battery volts, high battery volts, charge fail. |
Temperature Compensation |
N/A The optimum charge voltage for lead acid and NiCd batteries varies with ambient temperature. Sentinel can be configured to sense battery temperature from a remote sensor and automatically compensate the output charge voltage. |
Versatile |
N/A
Stock Code - 42.70.3619 Description - RTC sensor for remote temperature compensation feature, complete with 3 m/9.8 ft lead assembly. Non-standard lengths available to special order. Stock Code - 42.70.3825 Description - SNTL150P-PCCONN programming kit. Includes SNTL150P-PCSUITE software tool (PC compatible), USB-TTL interface and power/data connection leads. |
Installation and Connection |
N/A
Stock Code - 42.70.3619 Description - RTC sensor for remote temperature compensation feature, complete with 3 m/9.8 ft lead assembly. Non-standard lengths available to special order. Stock Code - 42.70.3825 Description - SNTL150P-PCCONN programming kit. Includes SNTL150P-PCSUITE software tool (PC compatible), USB-TTL interface and power/data connection leads. |
Accessories |
N/A
Stock Code - 42.70.3619 Description - RTC sensor for remote temperature compensation feature, complete with 3 m/9.8 ft lead assembly. Non-standard lengths available to special order. Stock Code - 42.70.3825 Description - SNTL150P-PCCONN programming kit. Includes SNTL150P-PCSUITE software tool (PC compatible), USB-TTL interface and power/data connection leads. |
Warranty |
N/A
All part numbers are supplied with output calibrated for vented lead-acid cells. Output calibration can be optimized for different battery types by using the SNTL150P-PCSUITE software tool. Dimensions for reference only. Use actual product for mounting template. For safe heat dissipation, mount product in orientation shown, with minimum air-gap clearance of 40 mm/1.5 in. above/below and 25 mm/1.0 in. at each side. |
Note |
N/A
All part numbers are supplied with output calibrated for vented lead-acid cells. Output calibration can be optimized for different battery types by using the SNTL150P-PCSUITE software tool. Dimensions for reference only. Use actual product for mounting template. For safe heat dissipation, mount product in orientation shown, with minimum air-gap clearance of 40 mm/1.5 in. above/below and 25 mm/1.0 in. at each side. |