- Open-frame (protective cover) Sentinel 300P
- Input supply 110/120/220/240 VAC (50 Hz/60 Hz)
- Output 10 A at 12/24 V
- Fire Pump Approved
Specifications
Power Supply
Alternate Current (AC) Operating Voltage |
N/A 95 to 250 V |
Operating Frequency |
N/A 47 to 63 Hz |
Direct Current (DC) Charge Output
Direct Current (DC) Nominal Voltage1 | N/A 12 V24 V |
Maximum Current Limit |
N/A 10 A |
Voltage Ripple |
N/A <1 % |
Line Regulation |
N/A <2 % |
Load Regulation |
N/A <2 % |
Rating (All Relays)
Maximum Current Rating at 30 Direct Current (DC) Voltage2 | N/A 1 A |
Standards for Maximum Current Rating at 30 Direct Current (DC) Voltage |
N/A UL Class 2 |
Physical
Operating Temperature |
N/A -40 to 60 ºC-40 to 140 ºF |
Display Viewability (Liquid Crystal Display (LCD) Models) |
N/A 0 to 50 ºC32 to 122 ºF |
Relative Humidity |
N/A 20 to 90 % |
Electrical Safety |
N/A 2006/95/EC |
Electromagnetic Compatibility |
N/A 2004/108/EC EN 55022 Class B (EN 61000-6-1, EN 61000-6-3) |
UL Approvals |
N/A BBGQ: UL1236, CSA22.2 no. 107.2 BBHH: UL1236 SE |
Dimensions
Overall Width (W) |
N/A 6.22 in158 mm |
Overall Height (H) |
N/A 8.19 in208 mm |
Overall Depth (D) |
N/A 3.31 in84 mm |
Fixing Holes (X) |
N/A 5.91 in150 mm |
Fixing Holes (Y) |
N/A 5.91 in150 mm |
Weight |
N/A 2.5 lb1.1 kg |
Standard Output Calibration
AutoBoost
AutoBoost |
N/A
Microprocessor programmability for automatic or manual configuration of charge output voltages (12 or 24 V nominal), cell types/numbers and application - all in one standard model. Programming is by circuit board links or PC - based software configuration and monitoring tool. |
Temperature Compensation
Temperature Compensation |
N/A
Microprocessor programmability for automatic or manual configuration of charge output voltages (12 or 24 V nominal), cell types/numbers and application - all in one standard model. Programming is by circuit board links or PC - based software configuration and monitoring tool. |
Flexible Configuration
Flexible Configuration |
N/A
Microprocessor programmability for automatic or manual configuration of charge output voltages (12 or 24 V nominal), cell types/numbers and application - all in one standard model. Programming is by circuit board links or PC - based software configuration and monitoring tool. |
Inputs and Outputs
Inputs and Outputs |
N/A
Options for backlit LCD readout, analogue metering and CAN 2.0B/SAE J1939 data communication; all models include RS485 communication for configuration and control. |
Display, Instrumentation and Communication
Display, Instrumentation and Communication |
N/A
Options for backlit LCD readout, analogue metering and CAN 2.0B/SAE J1939 data communication; all models include RS485 communication for configuration and control. |
Note
Note |
N/A
Tested and approved by UL to: UL1236 - Battery chargers for charging engine-starting batteries, and CSA22.2 No. 107.2 - Battery chargers. |
- 1 Programmable
- 2 Resistive load